Compact and cost-effective module with industry-proven I/Os

Comprehensive diagnostic functions ensure reliable and safe operation

sysWORXX CANopen IO-X1

The sysWORXX CANopen IO-X1 module is a highly compact and cost-effective CANopen I/O module featuring industrially proven I/O ports.

The CANopen I/O module contains a CPU core, including pre-programmed firmware for CANopen communication and the peripherals for industrial inputs and outputs. Comprehensive diagnostic functions ensure reliable and safe operation.

All inputs and outputs of the CANopen I/O module,&, as well as configuration parameters, are accessible via the CANopen protocol.

The sysWORXX CANopen I/O module is a CANopen slave device compliant with the CANopen device profile CiA 401 V2.1 and the CANopen communication profile CiA 301 V4.02. Two LEDs indicate the device status in accordance with CiA 303-3 V1.0.

Now also available in the Conrad online shop

  • Features & Details...
    Details

    Physical

     

    Dimensions (width, depth, height)

    95 x 70 x 58 mm

    Operating temperature

    -20 to +70°C

    Storage temperature

    -20 to +90°C

    Humidity

    10 to 95 per cent, non-condensing (VDE 0110)

    Weight

    approx. 130 g

    Mounting type

    DIN top-hat rail mounting

    Protection class

    IP20

    n

    Power supply

     

    Operating voltage

    24 V ± 20%

    Current consumption

    < 70 mA

    n

    I/O interfaces

     

    Digital inputs 24 VDC

    16 (galvanically isolated in groups of 4 channels each)

    Digital outputs 24 VDC, 0.5 A

    8 (transistor, high-side switch, short-circuit-proof with monitoring function and overheating protection)

    n

    Displays

     

    Status LEDs

    Power, Error, Module status, I/O status

  • CANopen properties...
    • CiA 301 V4.02 Communication Profile
    • Device Profile CiA 401 V2.1
    • Status indicators in accordance with CiA Standard 303-3 V1.0
    • Layer Setting Service (LSS) in accordance with CiA 305 V1.1
    • 2 TPDOs and 2 RPDOs
    • Dynamic PDO linking and mapping
    • SDO server
    • Life guarding, Node guarding, Heartbeat Producer
    • 5 heartbeat consumers
    • Emergency Producer
    • Minimum boot-up capability (slave)
    • Minimum NMT boot-up master (manufacturer extension)
  • Communications and device configuration...
    • Galvanically isolated CAN bus driver supports up to 110 CAN nodes on a single CAN bus
    • Jumper for 120-ohm CAN bus termination
    • Hex-encoding switches for configuring the node ID and baud rate
    • CAN bus bit rate: 10 kbit/s to 1 Mbit/s
    • High-quality connectors (lockable) included in the scope of delivery
      • Power supply: 2-pin connector
      • CAN bus: 5-pin connector
      • I/O: single 30-pin connector, lockable
    • Non-volatile memory for storing configuration data
    • Internal monitoring and diagnostics of: on-board temperature, power supply, memory controller and other parameters
    • Emergency alert
  • Documents & Downloads...
  • Order information...
    Bestellinformation

    Item No.

    Description

    3001000

    CANopen IO-X1, Standard Version

     

    Digital inputs: 16 channels, 24 V DC, galvanically isolated in groups of 4 channels each / Digital outputs: 8 channels, 24 V DC / 500 mA, high-side switch, short-circuit-proof

Get in touch now

Ralf Haag

Your contact person: Ralf Haag

Department: Sales Manager

Email: ralf.haag@systec-electronic.com
Phone: +49 3765 38600 1127
SYS TEC electronic sales team
Email: sales@systec-electronic.com
Phone: +49 3765 38600-2110

Search the website

The internal search function finds pages, documents and blog posts.
Please enter a search term.

What are you looking for?

Frequently searched for:

  • EMC testing
  • Project management
  • Prototype manufacturing
Cookies and Data Protection
Exit the dialogue box and return to the top of the page