sysWORXX I/O-X 3

Compact & cost effective CANopen remote I/O module

Extensive diagnostic functions ensure reliable & safe operation

The CANopen IO-X3 is a very compact and cost effective CANopen IO module featuring a high-density of industrial proven IO's.

The module includes a CPU-core including the pre-programmed firmware for CANopen communication and peripherals for the industrial inputs and outputs. Extensive diagnostic routines are implemented to ensure a most reliable and safe operation.

All inputs and outputs as well as configuration parameters are accessible via the CANopen protocol.

The CANopen IO-X3 is a CANopen slave device according CANopen device profile CiA 401 V2.1 and CANopen communication profile CiA 301 V4.02.

Two LED indicate the device state according to CiA 303-3 V1.0.

Module Features

toggle fullscreen
Physical 

Size (LxWxH)

95x70x58mm

Operating Temperature-20 to +70°C
Storage Temperature

-20 to +90°C

Humidity10 to 95% non-condensing (VDE 0110)
Weightca. 130g

Installation Method

DIN-rail mounting

Enclosure Protection ClassIP20

Power Supply

 

Operating Voltage

24V ± 20%

Current Consumption< 70mA
I/O Interfaces 

Digital Inputs 24 VDC, 500mA

24 (short circuit protected)

Visualisation 
Status LEDsPower
 Error
 Modul status
 I/O Status
 and others
Particularities 

CAN/CANopen

CANopen device according to CiA 401 V2.1

 

Galvanic isolated CAN bus interface

 

CAN bus termination (120 Ohm resistor) via Jumper

Others

Non-volatile storage of configuration data

 

Watchdog

 

Separated power supply pin for supply of digital output groups

 

CANopen Features

  • Communication profile according to CiA 301 V4.02
  • Device profile according to CiA 401 V1.2
  • State indicators according to CiA 303-3 V1.0
  • Layer Setting Service (LSS) according to CiA 305 V1.1
  • 2 RPDO
  • Dynamic PDO-Linking and Mapping
  • SDO-Server
  • Life guarding, Node guarding, Heartbeat Producer
  • 5 Heartbeat Consumers
  • Emergency Producer
  • Minimum Boot-up capability (Slave)
  • Minimum NMT boot-up master (Manufacturer extension)

Communication and device configuration:

  • Galvanic decoupled CAN-bus driver supports up to 110 CAN-nodes on one bus
  • Jumper for CAN-bus termination 120Ohm
  • Hex-encoding switches for setting node-ID and baud rate
  • CAN-bus baud rate: 10kBit/s to 1Mbit/s
  • High-quality connectors: (included in scope of delivery)
    • Power-Supply: 2-pin plug connector
    • CAN-bus: 5-pin plug connector
    • I/O: single 30-pin plug connector, lockable
  • Non-volatile memory for storage of configuration data
  • Internal monitoring and diagnostics of: onboard temperature, power supply, memory and other controller internals
  • Emergency Messages sent out in case of failure

Documents

NameTypeSizeAction
sysWORXX CANopen I/O modules - Product Flyer
pdf 987 KB Download
sysWORXX CANopen IO-X3 - Fact sheet
pdf 518 KB Download
sysWORXX CANopen I/O modules - User Manual
pdf 3 MB Download

Downloads

NameTypeSizeAction
EDS files - sysWORXX CANopen I/O modules
P/N SO-1064 - Package includes the "Electronic Data Sheet" (EDS) for all sysWORXX CANopen I/O modules
zip 26 KB Download

Ordering Information

Delivery contents / order number

Assembled and tested module, Connectors, Documentation, EDS-file, Demoversion of the CANopen configuration tools on CD

Available order numbers:

toggle fullscreen
P / NDescription

3001002

CANopen IO-X3, Standard version
Digital outputs: 24 channels, 24VDC / 500mA, high side switches with short circuit protection

 

Your Salesteam from SYS TEC electronic

We would be glad to help you.