Compact & cost effective module with industrially proven I/Os
Extensive diagnostic functions ensure reliable & safe operation
The CANopen IO-X1 is a very compact and cost effective CANopen IO module featuring a high-density of industrial proven I/O's.
The module includes a CPU-core including the pre-programmed firmware for CANopen communication and peripherals for the industrial inputs and outputs. Extensive diagnostic routines are implemented to ensure a most reliable and safe operation.
All inputs and outputs as well as configuration parameters are accessible via the CANopen protocol.
The CANopen IO-X1 is a CANopen slave device according CANopen device profile CiA 401 V2.1 and CANopen communication profile CiA 301 V4.02.
Two LED indicate the device state according to CiA 303-3 V1.0.
Module Features
Physical | |
Size (LxWxH) | 95x70x58mm |
Operating Temperature | -20 to +70°C |
Storage Temperature | -20 to +90°C |
Humidity | 10 to 95% non-condensing (VDE 0110) |
Weight | ca. 130g |
Installation Method | DIN-rail mounting |
SEnclosure Protection Class | IP20 |
Power Supply | |
Operating Voltage | 24V ± 20% |
Current Consumption | < 70mA |
I/O Interfaces | |
Digital Inputs 24 VDC | 16 (galvanic isolated 4 channels share same ground) |
Digital Outputs 24VDC, 0,5 A | 8 channels, 24VDC / 500mA high side switches with short circuit protection and monitoring, overheat protection |
PWM 24VDC, 0,5A | 2 |
Visualisation | |
Status LEDs | Power |
Error | |
Modul Status | |
I/O Status |
CANopen Features
- Communication profile according to CiA 301 V4.02
- Device profile according to CiA 401 V2.1
- State indicators according to CiA 303-3 V1.0
- Layer Setting Service (LSS) according to CiA 305 V1.1
- 2 TPDO and 2 RPDO
- Dynamic PDO-Linking and Mapping
- SDO-Server
- Life guarding, Node guarding, Heartbeat Producer
- 5 Heartbeat Consumers
- Emergency Producer
- Minimum Boot-up capability (Slave)
- Minimum NMT boot-up master (Manufacturer extension)
Communication and device configuration:
- Galvanic decoupled CAN-bus driver supports up to 110 CAN-nodes on one bus
- Jumper for CAN-bus termination 120 Ohm
- Hex-encoding switches for setting node-ID and baud rate
- CAN-bus bitrate: 10kbit/s to 1Mbit/s
- High-quality connectors (lockable): (included in scope of delivery)
- Power-Supply: 2-pin plug connector
- CAN-bus: 5-pin plug connector
- I/O: single 30-pin plug connector, lockable
- Non-volatile memory for storage of configuration data
- Internal monitoring and diagnostics of: onboard temperature, power supply, memory and other controller internals
- Emergency Messages sent out in case of failure
Downloads
Name | Type | Size | Action |
---|---|---|---|
E | |||
EDS files - sysWORXX CANopen I/O modules P/N SO-1064 - Package includes the "Electronic Data Sheet" (EDS) for all sysWORXX CANopen I/O modules | zip | 26 KB | Download |
Ordering Information
Delivery contents / order number
Assembled and tested module, Connectors, Documentation, EDS-file, Demoversion of the CANopen configuration tools on CD
Available order numbers:
P / N | Description |
3001000 | CANopen IO-X1,Standard version Digital Inputs: 16 digital inputs 24VDC, galvanic isolated in groups of 4 inputs / Digital Outputs: 8 digital outputs 24VDC/500mA, high side switch, short circuit protected |