PLC Device specification - OpenPCS Starter Kit
|
IO configuration
- 24 Digital inputs 24VDC, galvanic isolated
- 16 Digital outputs 24VDC/500mA, galvanic isolated, short-circuit
proof
- 4 Relay outputs 250VAC/2A
- 4 Analog inputs 0-10VDC (0-20mA), 10-Bit resolution
- 2 Analog outputs 0-10VDC, short-circuit proof
- 2 PWM outputs 24VDC/500mA
- 3 Fast counter inputs 24VDC (70kHz), galvanic isolated
Communication interfaces:
- 2 High-Speed CAN-bus interfaces according to CiA standard DS 102,
galvanic isolated
- 2 independent utilizable CANopen interfaces
- 3 RS232 interfaces, of these one full-modem capable
Memory:
- 32kB non-volatile memory for storage of user data
- 128kB PLC memory (shared for code and data)
LED indicators:
- IO states, Communication state, power and device state
Run/Stop/MRES switch
Power-supply:
- power-supply for CPU and IO separated, 24VDC (±20%) each
Connectors:
- High-Quality spring-type terminal connectors, separately removable
|
|
|
|